Introduction to the ODC-20 cabinet

Information on the ODC-20 cabinet description, features, options, access, and size follows.
General description of the ODC-20 cabinet
The Calix C7 ODC-20 cabinet is an environmentally controlled, aluminum and steel enclosure designed to deploy the Calix C7 in outdoor terminal locations. The cabinet can be configured for purely copper, fiber, or a combination of both with flexibility for field migration from copper to fiber.

The Calix ODC-20 cabinet consists of a main cabinet sitting on a battery compartment base. The main cabinet houses three compartments, an equipment compartment, splice compartment, and a copper protection and fiber compartment.

The Calix C7 ODC-20 cabinet is wired for delivery of copper or fiber-based services supporting up to 480 subscribers. The patent-pending integrated cooling system combines low power DC cooling blowers with advanced air-to-air tubular heat exchangers to dissipate large amounts of heat in very small spaces.

Door description of the outdoor cabinet

The cabinet has three doors - front, rear, and side - as well as battery compartment access panels in the front and rear.

All main compartment doors have 2-point position tamper-proof Telco hex-pin locks, each with provision for a padlock, if required by local site practice. The front battery compartment panel has two tamper-proof hex-key locks, each with provision for a padlock.

The rear door can be removed by accessing it from the front door. No external hardware or pad lock tab is present on the rear door. (Note: For the ODC-20 with the optional extended battery back-up configuration, the rear door has two tamper-proof hex key locks with provision for a pad lock.)

Front view of the ODC-20 cabinet

Features of the ODC-20 cabinet
Following are some features of the Calix C7 ODC-20:
 
  • integrated air-to-air tubular cooling system with DC blowers

  • wired capacity of up to 480 subscribers (copper and/or fiber)

  • environmentally rated -40C to +52C ambient temperature

  • standard 5-pin copper protection panels - up to 480 positions

  • 220-240 VAC single phase power feed

  • 60 Amp service with UL listed service disconnect

  • redundant AC feeds to rectifier, redundant DC feeds to Calix C7 shelf

  • low voltage DC disconnect

  • high power AC surge protection

  • extensive alarm functionality

  • UL-67 and GR-487 compliance

Options of the ODC-20 cabinet
Following are some options of the Calix C7 ODC-20:
 
  • Pole mount kit

  • Pad mount kit

  • 30 Amp Twist-Lock, and 60 Amp Pin and Sleeve-type generator connectors (with breaker/interlock)

  • Splice tray fiber management options

  • Fiber distribution panel options

  • Rectifier modules

  • Battery heater

Dimensions of the ODC-20 cabinet
 
Parameter Size - standard Size - metric
width 45 inches 114.3 centimeters
depth 33 inches 84 centimeters
height 55 inches 140 centimeters
weight 1000 pounds (1320 pounds equipped with Northstar batteries. Calix recommends and supports using Northstar 100 AH batteries.) 453.59 kilograms (598.74 kilograms equipped with Northstar 100 AH batteries)
 
 